Delta Electronics

PCS125HV

Legacy PCS · 1 exact configuration · California, US

Choose a configuration ↓
i

A registry listing is a starting point. CEC inclusion is not nationwide installation approval. Confirm the exact model and configuration with your utility and local authority.

How to use this data

Equipment overview

Inverter with PCS functionality

The figures below refer to PCS125HV {480V}. Use the configuration table for other variants.

Controlled apparent power
125 kVA
Operating voltage
480 V
PCS functionality
Inverter
Technology
Not reported

Specifications are reported in the CEC source; SolarApprovals has not independently tested this equipment. A missing value does not mean zero or a failed certification.

Exact configurations

CEC annotations in braces identify the listed configuration and are not part of the manufacturer’s model number. Variants share this canonical page.

Exact CEC configurations for PCS125HV
CEC model / configurationControlled apparent powerVoltage / displayObservationCompare
PCS125HV {480V}PCS Data for Inverter and ESS row 73125 kVA480 VListed in CEC

Source specifications and conditions

Additional source information for PCS125HV {480V}. Qualifiers, reported control modes and required devices are retained as written. Power-control listings do not establish arbitrary battery/inverter pairings.

Equipment type
Inverter
CEC listing date
2024-02-12
Export-only mode
Y
Import-only mode
Y
No-exchange mode
N
Unrestricted mode
N
Phase configuration
Multi
PCS CRD document date
2022-11-14
PCS CRD issuing entity
CSA Group
Additional required devices
ALH-0.66 External CTs
Output voltage as reported (V)
480
Export-only response time (seconds)
0.244
Import-only response time (seconds)
0.046
No-exchange response time (seconds)
N/A
Current measurement reference points
Inverter & External CTs
Unrestricted response time (seconds)
N/A
Maximum apparent power as reported (kVA)
125
Maximum continuous current as reported (A)
151

Documented compatibility

No specific equipment pairing has been verified for this model.

Shared voltage, a hybrid designation, or the same manufacturer does not establish compatibility. Check the manufacturer’s installation documents for exact model combinations, firmware, and operating conditions.

Registry observation history

Dates show when SolarApprovals observed a status. The first observation is not the original CEC listing date. History begins with our first import.

  • Sep 21, 2026 · California Energy CommissionFirst observed: Listed in CECPCS125HV {480V}
    Archived CEC source