Sigenergy Technology Co., Ltd.

SigenStor EC x SP US

Power control system · 2 exact configurations · California, US

Choose a configuration ↓
i

A registry listing is a starting point. CEC inclusion is not nationwide installation approval. Confirm the exact model and configuration with your utility and local authority.

How to use this data

Equipment overview

The PCS controller in the BESS system allows the export of active power from the BESS to the Area EPS but shall not allow the import of active power from the Area EPS for BESS charging purposes. This is the same as "No Grid Charge".

The figures below refer to SigenStor EC x SP US. Use the configuration table for other variants.

Controlled active power
11.5 kW
Operating voltage
240 V
PCS functionality
ESS Export Only Mode
Technology
Not reported

Specifications are reported in the CEC source; SolarApprovals has not independently tested this equipment. A missing value does not mean zero or a failed certification.

Exact configurations

CEC annotations in braces identify the listed configuration and are not part of the manufacturer’s model number. Variants share this canonical page.

Exact CEC configurations for SigenStor EC x SP US
CEC model / configurationControlled active powerVoltage / displayObservationCompare
SigenStor EC x SP USPower Control Systems row 10311.5 kW240 VListed in CEC
SigenStor EC x SP USPower Control Systems row 10411.5 kW240 VListed in CEC

Source specifications and conditions

Additional source information for SigenStor EC x SP US. Qualifiers, reported control modes and required devices are retained as written. Power-control listings do not establish arbitrary battery/inverter pairings.

Source notes
The letter x in the PCS model number and the inverter model number represents the nominal AC output power (kW) of the inverter, where x = blank, 11.4, 9.6, 7.6, 5.7, 4.8, and 3.8 The letter A in the ESS model number represents the power capacity (kW), where A = 11.5, 11.4, 9.6, 7.6, 5.7, 4.8, and 3.8. The letter B in the ESS model number represents the energy capacity (kWh), where B = 6.02, 9.04, 12.04, 15.06, 18.08, 21.08, 24.10, 27.12, 30.12, 33.14, 36.16, 39.16, 42.18, 45.20, 48.20, 51.22, and 54.24.
UL 3141 edition
OOI Issue 2 : 2024
CEC listing date
2026-05-21
PCS functionality
ESS Export Only Mode
Phase configuration
L-N/L-L
Integrated end product
Inverter
Scheduling conformance
No
UL 3141 certificate date
2026-04-16
UL 3141 certifying entity
CSA Group
Additional required devices
Energy Storage System (SigenStor-A-B), Sigen Backup Switch
Maximum controlled current (A)
48
Rated operating voltage(s) (V)
240
Time to steady state (seconds)
0.73
Maximum response time (seconds)
0.131
Current measurement reference points
Point Of Common Coupling (PCC)
Maximum controlled active power (kW)
11.5

Use the source row references above to inspect the conditions for each other configuration.

Documented compatibility

No specific equipment pairing has been verified for this model.

Shared voltage, a hybrid designation, or the same manufacturer does not establish compatibility. Check the manufacturer’s installation documents for exact model combinations, firmware, and operating conditions.

Registry observation history

Dates show when SolarApprovals observed a status. The first observation is not the original CEC listing date. History begins with our first import.

  • Sep 21, 2026 · California Energy CommissionFirst observed: Listed in CECSigenStor EC x SP US
    Archived CEC source
  • Sep 21, 2026 · California Energy CommissionFirst observed: Listed in CECSigenStor EC x SP US
    Archived CEC source